Model | PEFY-P80VMH-E-F | PEFY-P140VMH-E-F | PEFY-P200VMH-E-F | PEFY-P250VMH-E-F | ||
---|---|---|---|---|---|---|
Power source | 1-phase 220-240V 50Hz / 1-phase 208-230V 60Hz | 3-phase 380-415V 50Hz / 3N~ 380-415V 60Hz | ||||
Cooling capacity | kW*1 | 9.0 | 16.0 | 22.4 | 28.0 | |
BTU/h*1 | 30700 | 54600 | 76400 | 95500 | ||
Temp. range of cooling | 21°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 21°CD.B. |
21°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 21°CD.B. |
||||
Heating capacity | kW*1 | 8.5 | 15.1 | 21.2 | 26.5 | |
BTU/h*1 | 29000 | 51500 | 72300 | 90400 | ||
Temp. range of heating | -10°CD.B. ~ 20°CD.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 21°CD.B. |
-10°CD.B. ~ 20°CD.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 21°CD.B. |
||||
Power consumption |
Cooling *2 | kW | 0.16/0.21 | 0.29/0.33 | 0.34/0.42 | 0.39/0.50 |
Heating *2 | kW | 0.16/0.21 | 0.29/0.33 | 0.34/0.42 | 0.39/0.50 | |
Dimension H x W x D |
mm(in) | 380x1000x900 15×39-3/8×35-7/16 |
380x1200x900 15×47-1/4×35-7/16 |
470x1250x1120 18-9/16×49-1/4×44-1/8 |
||
Current | Cooling *2 | A | 0.67/0.91 | 1.24/1.48 | 0.58/0.74 | 0.68/0.86 |
Heating *2 | A | 0.67/0.91 | 1.24/1.48 | 0.58/0.74 | 0.68/0.86 | |
External finish | Galvanized | Galvanized | ||||
Net Weight | kg(lbs) | 50(111) | 67(148) | 100(221) | ||
Heat exchanger | Cross fin(Aluminium plate fin and copper tube) | Cross fin(Aluminium plate fin and copper tube) | ||||
Fan | Type x Quantity | Sirocco fan x 1 | Sirocco fan x 2 | Sirocco fan x 2 | ||
Airflow rate | cfm | 318 | 636 | 989 | 1236 | |
External static pressure *3 |
208V Pa | 35-85-170 | 35-85-170 | – | – | |
220V Pa | 40-115-190 | 50-115-190 | – | – | ||
230V Pa | 50-130-210 | 60-130-220 | – | – | ||
240V Pa | 80-170-220 | 100-170-240 | – | – | ||
380V Pa | – | – | 140/200 | 110/190 | ||
400V Pa | – | – | 150/210 | 120/200 | ||
415V Pa | – | – | 160/220 | 130/210 | ||
Motor | Type | 1-phase induction motor | – | – | ||
Output | kW | 0.09 (220V, 115Pa) | 0.14 (220V, 115Pa) | – | – | |
Air filter(option) | Synthetic fibre unwoven cloth filter(long life) | Synthetic fibre unwoven cloth filter(long life) | ||||
Refrigerant pipe diammeter |
Gas Flare |
mm(in) | 15.88(5/8) | 19.05(3/4) | 22.2(7/8) | |
Liquid Flare |
mm(in) | 9.52(3/8) | 9.52(3/8) | |||
Field drain pipe diameter | mm(in) | O.D. 32(1-1/4) | O.D. 32(1-1/4) | |||
Sound pressure level (measured in anechoic room)*2 *4 |
208,220V | dB(A) | 38 | 38 | 42 | 44 |
230-240V | dB(A) | 43 | 43 | 44 | 46 |
- *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition
-
Indoor Outdoor Pipe length Level difference Cooling 33°CDB/28°CWB
(91°FDB/82°FWB)33°CDB (91°FDB) 7.5 m (24-9/16 ft) 0m (0ft.) Heating 0°CDB/-2.9°CWB
(32°FDB/27°FWB)0°CDB/-2.9°CWB (32°FDB/27°FWB) 7.5 m (24-9/16 ft) 0m (0ft.) - *2 The values are measured at the factory setting of external static pressure. The figure of Electrical characteristic indicates at 240V 50Hz/230V 60Hz (PEFY-P80, 140VMH-E-F type), at 50Hz/60Hz (PEFY-P200, 250VMH-E-F type)
- *3 The factory setting of external static pressure is shown without < >. Refer to “Fan characteristics curves”, according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
- *4 Measured in anechoic room with a 1 m air inlet duct and 2 m air outlet duct attached to the unit and 1.5 m below the unit.
- Depending on the air conditioning load, outside temperature, and due to the activation of protection functions, the outlet air temperature may swing. Note that untreated outside air may be delivered directly into the room upon the activation of protection functions
- The maximum connectable indoor units to 1 outdoor unit are 110% (100% in case of heating below -5°C)
- When fresh air intake type indoor units connect to an outdoor unit together with other types of indoor unit, the total capacity of fresh air intake type indoor units needs to be 30% or less of the connected outdoor unit capacity
- Either a remote controller (sold separately) or a remote sensor (sold separately) must be installed to monitor the room temperature
- The AUTO mode on the local remote controller is available only when fresh air intake type indoor unit is connected to the R2 or WR2 series of outdoor unit.
- The system changeover function is available only when all the connected indoor units are fresh air intake type indoor units.
- The fan temporary stops during defrost.
- Dry mode is not available.
- In any case, the air flow rate should be kept lower than 110% of the above chart. Please see “Fan characteristics curves” in DATA BOOK for the details.
- When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
- Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation. Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also insulate rooms for dew condensation prevention as required.
- Air filter must be installed in the air intake side. The filter should be attached where easy maintenance in possible in case of usage of field supply filters.
Model | PEFY-P125VMHS-E-F | PEFY-P200VMHS-E-F | PEFY-P250VMHS-E-F *6 | ||
---|---|---|---|---|---|
Power source | 1-phase 220-230-240 V 50/60 Hz | ||||
Cooling capacity (Nominal) |
kW*1 | 14.0 | 22.4 | 28.0 | |
BTU/h*1 | 47800 | 76400 | 95500 | ||
Power Input *2 | kW | 0.220 | 0.260 | 0.350 | |
Current Input 220V *2 |
A | 1.43 | 1.66 | 2.16 | |
Temp. range of cooling | 17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 17°CD.B. | 17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 17°CD.B. | 17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is lower than 17°CD.B. | ||
Heating capacity (Nominal) |
kW *3 | 8.9 | 13.9 | 17.4 | |
BTU/h*3 | 30400 | 47400 | 59400 | ||
Power Input *2 | kW | 0.230 | 0.270 | 0.360 | |
Current Input 220V *2 |
A | 1.52 | 1.85 | 2.38 | |
Temp. range of heating | -10°CD.B. ~ 20°CD.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is higher than 20°CD.B. | -10°CD.B. ~ 20°CD.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is higher than 20°CD.B. | -10°CD.B. ~ 20°CD.B. * Thermo-off (FAN-mode) automatically starts if the outdoor temperature is higher than 20°CD.B. | ||
External Finish | Galvanized | ||||
External Dimension H x W x D |
mm | 380 x 1,195 x 900 | 470 x 1,250 x 1,120 | 470 x 1,250 x 1,120 | |
in. | 15 x 47-1/16 x 35-7/16 | 18-9/16 x 49-1/4 x 44-1/8 | 18-9/16 x 49-1/4 x 44-1/8 | ||
Net Weight | kg(lbs) | 49 (109) | 78 (172) | 81 (179) | |
Heat exchanger | Cross fin(Aluminium fin and copper tube) | ||||
FAN | Type x Quantity | Sirocco fan x 1 | Sirocco fan x 2 | Sirocco fan x 2 | |
External Static Pressure *4, 5 | Pa | 100-150-200-250 | |||
mmH2O | 10.2-15.3-20.4-25.5 | ||||
Motor Type | DC Motor | ||||
Motor Output | kW | 0.244 | 0.375 | 0.375 | |
Driving Mechanism | Direct-driven by motor | ||||
Air flow rate (Low-Mid-High) *4, 5 | Normal-airflow rate mode(m3/min) | 14.0 – 15.5 – 18.0 | 22.5 – 25.0 – 28.0 | 28.0 – 31.0 – 35.0 | |
High-airflow rate mode(m3/min) | 15.5 – 18.0 – 20.0 | 25.0 – 28.0 – 32.0 | 31.0 – 35.0 – 40.0 | ||
Normal-airflow rate mode(L/s) | 233 – 258 – 300 | 375 – 417 – 467 | 467 – 517 – 583 | ||
High-airflow rate mode(L/s) | 258 – 300 – 333 | 417 – 467 – 533 | 517 – 583 – 667 | ||
Normal-airflow rate mode(cfm) | 494 – 547 – 636 | 794 – 883 – 989 | 989 – 1095 – 1236 | ||
High-airflow rate mode(cfm) | 547 – 636 – 706 | 883 – 989 – 1,130 | 1095 – 1236 – 1412 | ||
Sound pressure level (measured in anechoic room) (Low-Mid-High) *2 |
Normal-airflow rate mode(dB[A]) | 34-37-41 | 35-38-41 | 38-40-44 | |
High-airflow rate mode(dB[A]) | 36-40-42 | 36-39-42 | 38-41-45 | ||
Air filter | Option: Synthetic fiber unwoven cloth filter (long life filter). Option: Synthetic fiber unwoven cloth filter (long life filter). | Option: Synthetic fiber unwoven cloth filter (long life filter). | |||
Refrigerant pipe diammeter |
Gas(R410A) | mm(in) | 15.88 (5/8) Brazed | 19.05 (3/4) Brazed | 22.22 (7/8) Brazed |
Liquid(R410A) | mm(in) | 9.52 (3/8) Brazed | 9.52 (3/8) Brazed | 9.52 (3/8) Brazed | |
Field drain pipe diameter | mm(in) | O.D.32 (1-1/4) | |||
Optional Parts | Drain pump kit | PAC-DRP10DP-E2 | PAC-KE06DM-F | PAC-KE06DM-F | |
Long life filter | PAC-KE89LAF | PAC-KE85LAF | |||
Filter box | PAC-KE140TB-F | PAC-KE250TB-F |
- *1 Cooling capacity indicates the maximum value at operation under the following condition. Cooling: Indoor 33°CDB/28°CWB, Outdoor 33°CDB. The set temperature of the remote controller is 18°C
- *2 The value are measured at the factory setting of airflow mode and external static pressure
- *3 Heating capacity indicates the maximum value at operation under the following condition. Heating: Indoor 0°CDB/-2.9°CWB, Outdoor 0°CDB/-2.9°CWB. The set temperature of the remote controller is 25°C.
- *4 The factory setting of airflow mode and external static pressure mode is shown without < >. Refer to “Fan characteristics curves”, according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
- *5 If the airflow rate is over the usable range, dew drop can be caused from the air outlet and the air flow rate is changed automatically because of the output down by the fan motor control. If the air flow rate is less than the usable range, condensation from the unit surface can be caused.
- *6 Regarding P250VMHS-E-F, the middle notch air flow rate is different from the spec value when the external static pressure setting is set to 100Pa. See “Fan characterics curves” in DATA BOOK for the details.
- The combination of fresh air intake type indoor units with other types of indoor units to handle internal thermal load which may cause the conflict of operation mode. It is not recommended when fresh air intake type indoor unit is connected to the Y or WY series
- Depending on the air conditioning load, outside temperature, and due to the activation of protection functions, the desired preset temperature may not always be achieved and the discharge temperature may swing. Note that untreated outside air may be delivered directly into the room upon the activation of protection functions
- Fresh air intake type indoor units cannot be connected to PUMY and cannot be connected to an outdoor unit together with PWFY series
- The maximum connectable indoor units to 1 outdoor unit are 110% (100% in case of heating below -5°C).
- When fresh air intake type indoor units connect to an outdoor unit together with other types of indoor unit, the total capacity of fresh air intake type indoor units needs to be 30% or less of the connected outdoor unit capacity
- The AUTO mode on the local remote controller is available only when fresh air intake type indoor unit is connected to the R2 or WR2 series of outdoor unit.
- The system changeover function is available only when all the connected indoor units are fresh air intake type indoor units.
- The fan temporary stops during defrost.
- The cooling and heating capacities are the maximum capacities that were obtained by operating in the above air conditions and with a refrigerant pipe of about 7.5 m and a level difference of 0 m.
- The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical information in DATA BOOK for the details.
- Thermo off (Fan) operation automatically starts either when temperature is lower than 17°CDB in cooling mode or when the temperature exceeds 20°CDB in heating mode.
- Dry mode is not available.
- When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
- Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation. Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also insulate rooms for dew condensation prevention as required.
- Air filter must be installed in the air intake side. The filter should be attached where easy maintenance is possible in case of usage of field supply filters.